See Tables Below for Capacity Chart and Model Explanation.
KUNKLE PRESSURE ASME SAFETY VALVES
KUNKLE MODELS 910, 911, 916 & 917
Orifice Size |
D |
E |
F |
G |
H |
J |
Area |
.1213 Sq. In. |
.2157 Sq. In. |
.3369 Sq. In. |
.553 Sq. In. |
.864 Sq. In. |
1.415 Sq. In. |
Set
PSIG |
SCFM
Air
UV |
SCFM
Air
UV |
SCFM
Air
UV |
SCFM
Air
UV |
SCFM
Air
UV |
SCFM
Air
UV |
325 |
727 |
1292 |
2018 |
3313 |
5176 |
8477 |
350 |
780 |
1388 |
2167 |
3558 |
5558 |
9103 |
375 |
834 |
1483 |
2316 |
3802 |
5941 |
9729 |
400 |
888 |
1579 |
2466 |
4047 |
6323 |
10355 |
425 |
941 |
1674 |
2615 |
4292 |
6705 |
10982 |
450 |
995 |
1769 |
2764 |
4537 |
7088 |
11608 |
475 |
1049 |
1865 |
2913 |
4781 |
7470 |
12234 |
500 |
1102 |
1960 |
3062 |
5026 |
7853 |
12861 |
550 |
1210 |
2151 |
3360 |
5516 |
|
600 |
1317 |
2342 |
3658 |
6005 |
650 |
1425 |
2533 |
Valve Selection:
To Determine Valve Size
1. Locate Desired Pressure and SCFM
2. Intersect Orifice Size at the Top of the Chart
Example: Requirements 1102 scfm @ 500PSIG
Orifice, Model 910BD, |
700 |
1532 |
2724 |
750 |
1639 |
2915 |
800 |
1747 |
3106 |
850 |
1849 |
3298 |
900 |
1957 |
3489 |
V = Section 1
UV = Section VIII
 |
return to top
© 2008-2009 Midwest Control |
|
|
|
|
|
|