The Alternating Relays Are Used to Alternate the Use of 2 Motor Circuits. When the Coil is Energized the First Time, One Contact Closes and Will Open When the Coil is De-Energized. When the Coil is Energized Again the Other Contact Will Close and Will Open When the Coil is De-Energized. The Contacts From the Alternators Are to Be Used In the Control Circuit of Starters That Control Pumps or Compressor Motors.
- Can Be Wired In A Control Panel or As a Separate Unit
- NEMA A600 Rated Fixed Contacts
- UL Listed, CSA and CE Certified
- SPST Contacts
- Compact Design 45mm Wide
- Can Be Mounted on 35mm DIN 3 Track or Direct Panel Mount
Functional diagram
Mini-control relays with alternating contacts CA2SKE20

The Schneider Electric Alternator Uses Two SPDT Contacts to Switch the Load.
To Match Wiring When Replacing A Hubbell Alternator
(Which Uses a SPDT Contact Arrangement) Jumper Pins 13 & 23 On the Schneider Electric Alternator.
Dimensions

Scroll Down to View the Environment and Control Circuit Characteristics
Environment
Rated Insulation Voltage |
Conforming to IEC 947,
VDE0110 gr C,
BS 5424,
CSA 22-2n°14, UL 508 |
690V |
Conforming to Standards |
|
IEC 947, NF C 64-110 ,VDE 0660, BS 5424 |
Approvals |
|
UL Listed, CSA & CE Certified |
Protective Treatment |
Conforming to IEC 68
(DIN 50015) |
“TC” (Klimafest, Climate Proof) |
Degree of Protection |
Conforming to VDE 0106 |
Protection Against Direct Finger Contact |
Ambient Air Temperature
Around The Device |
Storage |
-50°C to +70°C (-76°F to 158°F) |
Operation |
-20°C to + 50°C (14°F to 122°F) |
Maximum Operating Altitude |
Without Derating |
6252 Feet (2000m) |
Operating Position |
 |
Cabling Screw
Clamp Terminals |
Solid Conductor |
Minimum |
Maximum |
|
#16 AWG
2 x 1.5 mm2 |
|
|
Flexible Cable without Cable End |
|
|
|
|
Flexible Cable with
Cable End |
|
|
|
|
Tightening Torque |
n°1 Head |
7.08 lbf-in (0.8 N● m) |
|
|
|
Control Circuit Characteristics
Related Control Circuit Voltage (Uc) |
|
24-400 V |
Control Voltage Limits
≤ 122 ° F (50° C) Single Voltage Coil |
For Operation |
0.85-1.1Uc |
For Drop-Out |
≥ 0.20Uc |
Average Coil Consumption
at 68 ° F (20 ° C) and at Uc
|
Inrush |
23 VA |
Sealed |
4.9 VA |
Heat Dissipation |
|
1.5 W |
Operating Time
at 20 ° C and at Uc
|
Between Coil Energization And:
- Closing of the N/O Contacts
|
8-16 ms |
Between Coil De-Energization And:
- Opening of the N/O Contacts
|
8-10 ms |
Maximum Operating Rate |
In Operating Cycles Per Hour |
1200 |
Mechanical Durability at Uc In Millions
of Operating cycles
|
50/60 Hz Coil |
10 |
|
Part No. |
Volts
60Hz |
Operating Range |
CA2SKE20-G7 |
120 |
102V-120V |
CA2SKE20-M7 |
208/220 |
187V-220V |
CA2SKE20-U7 |
230/240 |
204V-240V |
CA2SKE20-T7 |
480 |
408V-480V |
NEMA 1 General Purpose Enclosure |
CA2SKE20-G7NE |
120 |
102V-120V |
CA2SKE20-M7NE |
208/220 |
187V-220V |
CA2SKE20-U7NE |
230/240 |
204V-240V |
CA2SKE20-T7NE |
480 |
408V-480V |
Enclosure Only 8Lx6Wx4H |
ASE8X6X4 |
|
|
*** When Selecting the Alternating Relay Choose the Model Number Closest to Your Operating Voltage.
Coils Can Operate Within a 15% Range. Do Not Exceed Your Operating Voltage As the Life of the Coil Will Be Shortened.
|